Honeywell Flame Amplifier R7847A1025

  • Extended Product Type : Other
  • Product ID : R7847A1025
  • Honeywell Type Designation : Other

Features

  • Flame failure response time of 0.8 or 3.0 seconds.
  • Flame signal strength ranges from 0.0 to 5.0 Vdc.
  • Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
  • Flame signal test jacks to measure amplifier flame signal voltage.
  • Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
  • Compatible with existing Honeywell flame detectors (order separately).

Specification of Honeywell R7847A1025

  • Flame Failure Response Time (sec) : 0.8 sec or 1.0 sec
  • Use With Primary Safety Control : 7800 SERIES Relay Modules
  • Use With Flame Sensor : Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179